LAB
REVIEW AND
DUCT EROSION TEST Tests were performed in compliance with UL 181 and ASTM C-1071. The tests consisted of duct free blow of 10,000 feet/minute for one hour, and a four hour test at 10,000 feet/minute.
The duct liner sections were assembled and connected to the AMCA (fig.
5.5) test setup and (fig. 6.5) flow measurement apparatus, on the
downstream end of the tapered transition.
Air flow was increased from zero (0) until a center line velocity
of not less than 10,000 feet/minute was obtained.
Velocity was measured by means of a Pitot Tube (at the end of the
duct) connected to a portable manometer.
We ran a duct free blow for one (1) hour checking velocity
periodically. At the end of
the hour, we positioned a cheesecloth collector approximately 1 foot
downstream of the end of the duct. We
then ran a 4 hour test checking for anomalies at one (1) hour intervals.
(At each hour interval, velocity was checked to be sure a 10,000
feet/minute minimum was maintained.) Every hour during the test the
collector was inspected for erosion, using tape.
No noticeable anomaly on the tape determined a successful
completion of the test. Following
on the next page is a list of materials and duct construction used in the
test. Upon completion of the testing, there was no constant or increasing rate of erosion. There was no visual evidence of flaking or delamination of the air stream surface.
The
test was deemed successful based on the criterion designated in UL181 and
ASTM C-1071. MATERIAL
AND DUCT DESCRIPTION
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||